Mechanical Installation; Electrical Installation; Start-Up - ABB ACS580 Series Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580 Series:
Table of Contents

Advertisement

Mechanical installation

All brake resistors must be installed outside the drive. Follow the resistor
manufacturer's instructions.

Electrical installation

Checking the insulation of the assembly
Follow the instructions given in section
R1...R3 (page 131)
Connection diagram
See section
Connection diagram (page 139)
(North America).
Connection procedure
See section
Grounding shelf (page
Connect the thermal switch of the brake resistor as described in
system against thermal overload (page

Start-up

Start-up
WARNING!
Make sure that there is sufficient ventilation. New brake resistors can have
a protective grease coating. When the resistor warms up for the first time,
the grease burns off and can produce some smoke.
Set the following parameters (Standard control program):
Set parameter 30.30 Overvoltage control to disable.
Set parameter 31.01 External event 1 source to point to the digital input where
the thermal switch of the brake resistor is wired.
Set parameter 31.02 External event 1 type to Fault.
Set parameter 43.06 Brake chopper function to Enable. If you select Enabled
with thermal model, set also the brake resistor overload protection parameters
43.08 and 43.09 according to the application.
Check the resistance value of parameter 43.10 Brake resistance.
With these parameter settings, the drive stops by coasting on brake resistor
overtemperature.
or
Brake resistor assembly for R1...R3 (page 175)
Brake resistor assembly for
(IEC) or
Connection diagram (page 184)
146).
404).
Resistor braking 405
(North America).
Protecting the

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs580-01 seriesAcs580-01-293a-4+j400

Table of Contents