Circuit breakers (UL)

These drives are suitable for use on a circuit capable of delivering not more than
65 kA symmetrical amperes (rms) at 240 / 480 / 600 V maximum (100 kA
symmetrical amperes (rms) for IP66 (UL Type 4X) drives with disconnect and fuse
option at 240 / 480 / 600 V maximum), when protected by appropriate circuit
breakers in the tables below. Additional fuse protection is not required by UL when
using circuit breakers herein. Circuit breakers are not required to be in the same
enclosure as the drive.
Notes below the tables must be followed when using these breakers.
ACS580-
Frame
Input
01-...
size
current
3-phase U 1 = 200...240 V, P n at U n = 208/230 V, 60 Hz
04A6-2
R1
4.6
06A6-2
R1
6.6
07A5-2
R1
10A6-2
R1
10.6
017A-2
R1
16.7
024A-2
R2
24.2
031A-2
R2
30.8
046A-2
R3
46.2
059A-2
R3
59.4
075A-2
R4
74.8
088A-2
R5
88.0
114A-2
R5
114
143A-2
R6
143
169A-2
R7
169
211A-2
R7
211
273A-2
R8
273
¤ Enclosure minimum volume is not applicable
See notes 1-11 below
CB
maximum
voltage
current
A
A
25
25
7.5
25
25
25
40
40
100
100
100
150
150
200
300
300
400
CB
Enclosure
minimum
volume
volume
in 3
V
240
¤
240
¤
240
¤
240
¤
240
¤
240
¤
240
¤
240
¤
240
¤
240
¤
240
¤
240
¤
240
¤
240
¤
240
¤
240
¤
Technical data 303
Drive
ABB circuit breaker
in 3
65 kA @ 240 V
561
XT2Nαβ025#********
561
XT2Nαβ025#********
561
XT2Nαβ025#********
561
XT2Nαβ025#********
561
XT2Nαβ025#********
737
XT2Nαβ040#********
737
XT2Nαβ040#********
1390
XT2Nαβ100#********
1390
XT2Nαβ100#********
2027
XT2Nαβ100#********
2181
XT4Nαβ150#********
2181
XT4Nαβ150#********
2880
XT4Nαβ200#********
3369
XT5Nαβ30A#********
3369
XT5Nαβ30A#********
3858
XT5Nαβ40A#********