Requirements for non-ABB motors, P

See also
Abbreviations (page
Motor type
Nominal AC line
Random-wound
and form-wound
1) If the intermediate DC circuit voltage of the drive is increased from the nominal level due to long term
resistor braking cycles, check with the motor manufacturer if additional output filters are needed.
Guidelines for planning the electrical installation 101
102).
voltage
Motor insu-
lation sys-
U n ≤ 420 V
Standard:
Û LL =
1300 V
420 V < U n ≤
Standard:
500 V
Û LL =
1300 V
Reinforced:
Û LL =
1600 V,
0.2 µs rise
500 V < U n ≤
Reinforced:
600 V
Û LL =
1600 V
Reinforced:
Û LL =
1800 V
600 V < U n ≤
Reinforced:
690 V
Û LL =
1800 V
Reinforced:
Û LL = 2000
V, 0.3 µs
rise time
> 100 kW (134 hp)
n
Requirement for
ABB d u /d t and common mode filters, in-
sulated N-end motor bearings
tem
100 kW ≤ P n < 350
kW
or
IEC 315 ≤ frame size
< IEC 400
134 hp ≤ P n < 469
hp
or
NEMA 500 ≤ frame
size ≤ NEMA 580
+ N or CMF
+ d u /d t + (N or
CMF)
+ N or CMF
time
+ d u /d t + (N or
CMF)
+ N or CMF
+ d u /d t + N
+ N + CMF
1)
P n ≥ 350 kW
or
frame size ≥
IEC 400
P n ≥ 469 hp
or
frame size >
NEMA 580
+ N + CMF
+ N + d u /d t + CMF
+ N + CMF
+ N + d u /d t + CMF
+ N + CMF
+ N + d u /d t + CMF
+ N + CMF