Default I/O Connection Diagram - ABB ACS580 Series Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580 Series:
Table of Contents

Advertisement

218 Control unit

Default I/O connection diagram

The default I/O connections of the ABB Standard macro are shown below.
R1...R5
Connection
X1 Reference voltage and analog inputs and outputs
1...10 kohm
Max.
500 ohm
X2 & X3 Aux. voltage output and programmable digital inputs
7)
X6, X7, X8 Relay outputs
1
2
1
2
3
3
4
4
5
6
5
7
6
8
9
7
8)
8
9
10
10
11
6)
12
11
13
12
14
15
13
16
14
17
18
15
16
17
18
Term
SCR
Signal cable shield (screen)
AI1
Output frequency reference: 0...10 V
1) 3)
AGND
Analog input circuit common
+10V
Reference voltage 10 V DC
AI2
Not configured
AGND
Analog input circuit common
AO1
Output frequency: 0...20 mA
AO2
Motor current: 0...20 mA
AGND
Analog output circuit common
+24V
Aux. voltage output +24 V DC, max.
250 mA 2)
DGND
Aux. voltage output common
DCOM
Digital input common for all
DI1
Stop (0) / Start (1)
DI2
Forward (0) / Reverse (1)
Constant frequency selection 4)
DI3
Constant frequency selection 4)
DI4
Ramp set 1 (0) / Ramp set 2 (1) 5)
DI5
DI6
Not configured
Description

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs580-01 seriesAcs580-01-293a-4+j400