Guidelines For Installing The Drive To A Tt System - ABB ACS580 Series Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580 Series:
Table of Contents

Advertisement

134 Electrical installation – Global (IEC)
Note: These are the EMC filter and varistor screws of different drive frame sizes.
Frame size
R1...R3
R4 v2
R4...R5
R6...R9

Guidelines for installing the drive to a TT system

The drive can be installed to a TT system under these conditions:
1.
Residual current device has been installed in the supply system.
2. These screws have been disconnected. Otherwise EMC filter and
ground-to-phase varistor capacitor leakage current will cause the residual
current device to trip.
Frame size
R1...R3
R4 v2
R4...R5
R6...R9
Note:
Because the EMC filter screws have been disconnected, ABB does not guarantee
the EMC category.
ABB does not guarantee the functioning of the ground leakage detector built
inside the drive.
In large systems the residual current device can trip without a reason.
EMC filter screws
EMC screw
Two EMC screws
Two EMC screws
EMC filter screws
EMC screw
Two EMC screws
Two EMC screws
Ground-to-phase varistor screws
Ground-to-phase varistor screws
L1
L2
L3
N
Drive
VAR
VAR
VAR
VAR
VAR
VAR