134 Electrical installation – Global (IEC)
Note: These are the EMC filter and varistor screws of different drive frame sizes.
Frame size
R1...R3
R4 v2
R4...R5
R6...R9
■
Guidelines for installing the drive to a TT system
The drive can be installed to a TT system under these conditions:
1.
Residual current device has been installed in the supply system.
2. These screws have been disconnected. Otherwise EMC filter and
ground-to-phase varistor capacitor leakage current will cause the residual
current device to trip.
Frame size
R1...R3
R4 v2
R4...R5
R6...R9
Note:
•
Because the EMC filter screws have been disconnected, ABB does not guarantee
the EMC category.
•
ABB does not guarantee the functioning of the ground leakage detector built
inside the drive.
•
In large systems the residual current device can trip without a reason.
EMC filter screws
EMC screw
Two EMC screws
Two EMC screws
EMC filter screws
EMC screw
Two EMC screws
Two EMC screws
Ground-to-phase varistor screws
Ground-to-phase varistor screws
L1
L2
L3
N
Drive
VAR
VAR
VAR
VAR
VAR
VAR