Fuses (Ul) - ABB ACS580 Series Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580 Series:
Table of Contents

Advertisement

ACS580-
01-...
ABB type
046A-4
S 203P-B/C/Z 50
062A-4
S 803S-B/C 80
073A-4
S 803S-B/C 80
088A-4
S 803S-B/C 100
089A-4
S 803S-B/C 100
106A-4
S 803S-B/C 125
145A-4
XT4 L 250 Ekip LS/I
In=250 3p F F
169A-4
XT4 L 250 Ekip LS/I
In=250 3p F F
206A-4
T4 L 320 PR221DS-LS/I
In=320 3p F F
246A-4
T5 L 400 PR221DS-LS/I
In=400 3p F F
293A-4
T5 L 630 PR221DS-LS/I
In=630 3p F F
363A-4
T5 L 630 PR221DS-LS/I
In=630 3p F F
430A-4
T5 L 630 PR221DS-LS/I
In=630 3p F F
1) Trip characteristic Z is recommended

Fuses (UL)

Fuses for branch circuit protection per NEC are listed below. ABB recommends
fast acting class T or faster fuses in the USA. Obey local regulations.
For IP66 (UL Type 4X) drives that include the disconnect and fuse option, no branch
circuit protection is required external to the drive. Fuses shown in this table are
included inside the drive.
MCBs and MCCBs
1)
Max.
short-
circuit
I sc
kA
12
50
50
50
50
50
65
65
65
65
65
65
65
T max
T max
Electronic
frame
rating
release
XT / T
class
A
A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
XT4
250
250
XT4
250
250
T4
320
320
T5
400
400
T5
630
630
T5
630
630
T5
630
630
Technical data 299
SACE ordering
code for breaker
and release unit
A
N/A
N/A
N/A
N/A
N/A
N/A
1SDA068555R1
1SDA068555R1
1SDA054141R1
1SDA054365R1
1SDA054420R1
1SDA054420R1