Ambient Conditions - ABB ACS580 Series Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580 Series:
Table of Contents

Advertisement

350 Technical data

Ambient conditions

Environmental limits for the drive are given below. The drive is to be used in a
heated, indoor, controlled environment
coated.
Installation site altitude
Air temperature
Relative humidity
Contamination levels
Chemical gases
Solid particles
3)
. All printed circuit boards are conformal
Operation
installed for
stationary use
• 0...4000 m
(13123 ft) above
1)
sea level
• 0...2000 m (6561
ft) above sea
2)
level
Output derated
above 1000 m (3281
ft), see section
Alti-
tude derat-
ing (page
282).
-15...+50 °C
(5...122 °F).
0...-15 °C (32...5 °F):
No frost allowed.
See section
Electric-
al ratings (page
266).
5...95%
No condensation allowed. Maximum allowed relative humidity
is 60% in the presence of corrosive gases.
IEC 60721-3-3:
2002:
Classification of en-
vironmental condi-
tions - Part 3-3:
Classification of
groups of environ-
mental parameters
and their severities
- Stationary use of
weather protected
locations
Class 3C2
Class 3S2. No con-
ductive dust al-
lowed.
Storage
in the package
-
-40...+70 °C
(-40...+158 °F)
Max. 95%
IEC 60721-3-1: 1997
Class 1C2
Class 1S3 (packing
must support this,
otherwise 1S2)
Transportation
in the package
-
-40...+70 °C
(-40...+158 °F)
Max. 95%
IEC 60721-3-2: 1997
Class 2C2
Class 2S2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs580-01 seriesAcs580-01-293a-4+j400

Table of Contents