Deratings - ABB ACS580 Series Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580 Series:
Table of Contents

Advertisement

must be higher than or equal to the rated motor power. The power ratings are the
same regardless of the supply voltage within one voltage range.
Note: The ratings apply at ambient temperature of 40 °C (104 °F) for I
(NEC)). Above theses temperatures derating is required.
Note: The DriveSize dimensioning PC tool available from ABB
(http://new.abb.com/drives/software-tools/drivesize) is recommended for
selecting the drive, motor and gear combination.

Deratings

The output load capacity ( I
certain situations. In situations, where full motor power is required, oversize the
drive so that the total derated output current provides sufficient capacity to supply
the required nominal voltage to run the motor.
Note: The DriveSize dimensioning PC tool available from ABB
(http://new.abb.com/drives/software-tools/drivesize) is also suitable for derating.
Note: If several situations are present at a time, the effects of derating are
cumulative:
I
(derated) or I
(derated) or I
2
Ld
derating) x (altitude derating) x (ambient temperature derating), where no derating
= 1.0.
Note: The motor may have a derating on it too.
Example 1, IEC: How to calculate the derated current
The IP21 / UL Type 1 drive type is ACS580-01-062A-4, which has drive output current
of 62 A. Calculate the derated drive output current ( I
at 1500 m altitude and at 50 °C ambient temperature as follows:
1.
Switching frequency derating by derating factor (page
No derating needed for 4 kHz.
2.
Altitude derating (page
The derating factor for 1500 m is 1 - 1/10 000 m · (1500 - 1000) m = 0.95.
The derated drive output current becomes I
3.
Surrounding air temperature derating, IP21 (UL Type 1) (page
The derating factor for 50 °C ambient temperature = 0.90.
The derated drive output current becomes then I
Example 1, UL (NEC): How to calculate the derated current
The IP21 / UL Type 1 drive type is ACS580-01-052A-4, which has drive output current
of 52 A. Calculate the derated drive output current ( I
at 4921 ft (1500 m) altitude and at 50 °C ambient temperature as follows:
, I
, I
; note that I
2
Ld
Hd
(derated) = ( I
Hd
282):
Technical data 277
is not derated) decreases in
max
or I
or I
) x (switching frequency
2
Ld
Hd
) at 4kHz switching frequency,
2
283):
= 0.95 · 62 A = 58.9 A.
2
= 0.90 · 58.9 A = 53.01 A.
2
) at 4kHz switching frequency,
Ld
( I
for UL
2
Ld
279):