274 Technical data
ACS580-
Frame size
01-...
09A0-6
R2
011A-6
R2
017A-6
R2
022A-6
R3
027A-6
R3
032A-6
R3
041A-6
R5
052A-6
R5
062A-6
R5
077A-6
R5
099A-6
R7
125A-6
R7
144A-6
R8
192A-6
R9
242A-6
R9
271A-6
R9

Definitions

U n
Nominal output voltage of the drive. For input voltage range [ U 1 , see section
Electrical power network specification (page
60 Hz for UL (NEC) ratings.
I 1
Nominal input current (rms) at 40 °C (104 °F).
I max
Maximum output current. Available for two seconds at start.
I Ld
Continuous rms output current allowing 10% overload for 1 minute every 10
minutes
P Ld
Typical motor power in light-duty use (10% overload). The horsepower (hp)
ratings apply to most NEMA 4-pole motors.
Input
Max.
rating
current
I 1
I max
A
A
9.0
12.2
11.0
16.2
17.0
23.0
22.0
30.6
27.0
39.6
32.0
48.6
41.0
58
52
74
62
94
77
112
99
139
125
178
144
225
192
259
242
346
271
411
Output ratings
Light-duty use
I Ld
P Ld
A
hp
9.0
7.5
11.0
10
17.0
15
22.0
20
27.0
25
32.0
30
41.0
40
52
50
62
60
77
75
99
100
125
125
144
150
192
200
242
250
271
250
342). 50 Hz for IEC ratings and
Heavy-duty use
I Hd
P Hd
A
hp
6.1
5.0
9.0
7.5
11.0
10
17.0
15
22.0
20
27.0
25
32.0
30
41.0
40
52
50
62
60
77
75
99
100
125
125
144
150
192
200
242
250

Advertisement