Activation Switch; Cable Types And Lengths; Grounding Of Protective Shields - ABB ACS580 Series Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580 Series:
Table of Contents

Advertisement

416 The Safe torque off function

Activation switch

In the wiring diagrams, the activation switch has the designation [K]. This
represents a component such as a manually operated switch, an emergency stop
push button switch, or the contacts of a safety relay or safety PLC.
In case a manually operated activation switch is used, the switch must be of
a type that can be locked out to the open position.
The contacts of the switch or relay must open/close within 200 ms of each
other.
A CPTC thermistor protection module or an FSPS safety functions module can
also be used. For more information, see the module documentation.

Cable types and lengths

ABB recommends double-shielded twisted-pair cable.
Maximum cable lengths:
300 m (1000 ft) between activation switch [K] and drive control unit
60 m (200 ft) between multiple drives
60 m (200 ft) between external power supply and first control unit
Note: A short-circuit in the wiring between the switch and an STO terminal causes
a dangerous fault. Therefore, it is recommended to use a safety relay (including
wiring diagnostics) or a wiring method (shield grounding, channel separation)
which reduces or eliminates the risk caused by the short-circuit.
Note: The voltage at the STO input terminals of the drive must be at least 13 V DC
to be interpreted as "1".
The pulse tolerance of the input channels is 1 ms.

Grounding of protective shields

Ground the shield in the cabling between the activation switch and the control
unit at the control unit only.
Ground the shield in the cabling between two control units at one control unit
only.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs580-01 seriesAcs580-01-293a-4+j400

Table of Contents