Start-Up; Setting The Parameters - ABB ACS580 Series Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580 Series:
Table of Contents

Advertisement

440 Optional I/O extension and adapter modules
+10 V
-10 V
+10 V
-10 V

Start-up

Setting the parameters

1.
Power up the drive.
2. Verify that the diagnostic LED is on.
Parameter setting example for AI1
This example shows how to set the control unit parameters for a bipolar speed
reference ranging from -50 Hz to 50 Hz, with detection of a wire break between
the adapter module and the control unit of the drive.
Parameter
12.17 AI1 min
12.18 AI1 max
12.19 AI1 scaled at AI1 min
12.20 AI1 scaled at AI1 max
32.05 Supervision 1 function
32.06 Supervision 1 action
32.07 Supervision 1 signal
32.09 Supervision 1 low
CBAI-01
80
AI3+
AO3
81
AI3-
AGND
82
SCR
SCR
83
AI4+
AO4
84
AI4-
AGND
85
SCR
SCR
Setting
0.5 V
9.5 V
-50
50
Low
Fault
AI1
0.4
CCU-23/24
1
0...10 V
86
2
87
3
88
0...10 V
89
5
90
6
91
Default
4.000 mA or 0.000 V
20.000 mA or 10.000 V
0.000
50
Disabled
No action
Frequency
0.00
SCR
AI1
AGND
AI2
AGND