Input Power Cable - ABB ACS580 Series Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580 Series:
Table of Contents

Advertisement

144 Electrical installation – Global (IEC)

Input power cable

8. Cut an adequate hole into the rubber grommet. Slide the grommet onto the
cable.
Frame R1: Make sure there is no optional I/O extension module installed in
option slot 2 at this point.
IP66 (UL Type 4X) drives: Attach the cable gland to the hole and tighten nut
on the inside.
9. Prepare the ends of the cable as illustrated in the figure.
Note: The bare shield will be grounded 360 degrees. Mark the pigtail made
from the shield as a PE conductor with yellow-and-green color.
10. Slide the cable through the hole in the cable entry and attach the grommet to
the hole.
IP66 (UL Type 4X) drives: Tighten the cable gland nut on the outside.
WARNING!
If you install IP66 (UL Type 4X) drive indoors or outdoors in a wet, dirty,
dusty, corrosive or similar environment, all cables, conduits and fittings
must be approved for use in this type of environment. Tighten the fittings
properly to the drive to prevent leakage. If you ignore these instructions,
injury or death, or damage to the equipment can occur.
PE
PE
11. Connect the input power cable:
Ground the shield 360 degrees by tightening the clamp of the power cable
grounding shelf onto the stripped part of the cable (11a).
Connect the twisted shield of the cable to the grounding terminal (11b).
Connect the additional PE conductor of the cable (11c) (see the note in
section
Additional instructions and notes (page
Connect the phase conductors of the cable to the L1, L2 and L3 terminals.
Tighten the screws to the torque given below in the table (11d).
9
8
10
25)).