Motor Cable - ABB ACS580 Series Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580 Series:
Table of Contents

Advertisement

2. Attach the residual voltage warning sticker in the local language.
R1
2
3. Remove the rubber grommets for the motor and input power cables, as well
as brake resistor cable, if used.
Remove the grommets for the control cables when you are connecting them.
3
Note: The drive is shipped with grommet cones pointing up. They must be
removed and inserted back pointing down.

Motor cable

4. Cut an adequate hole into the rubber grommet. Slide the grommet onto the
cable.
5. Prepare the ends of the cable as illustrated in the figures. In frames R1 and R2
there are markings on the drive frame near the power cable terminals helping
you to strip the wires to the correct length of 8 mm.
Two different motor cable types are shown (5a, 5b).
IP66 (UL Type 4X) drives: Attach the cable gland to the hole and tighten nut
on the inside.
Note: The bare shield will be grounded 360 degrees. Mark the pigtail made
from the shield as a PE conductor with yellow-and-green color.
Electrical installation – Global (IEC) 141
R2
2
R3...R4
2