200 Electrical installation – North America
Note 1 for frames R8...R9: If you connect only one conductor to the connector,
ABB recommends that you put it under the upper pressure plate. If you use
parallel power cabling, put the first conductor under the lower pressure plate
and the second under the upper one.
Note 2 for frames R8...R9: The connectors are detachable but ABB does not
recommend that you detach them. If you do, detach and reinstall the connectors
as described in
Input power cabling
11. Strip the ends of the conductors.
Conduit
12. Slide the conductors through the conduit.
13. Connect the conductors:
•
Connect the grounding conductor to the grounding terminal (13a).
•
Connect the conductors as for the motor cabling. Use terminals L1, L2 and
L3. Tighten the screws to the torque given in the table (13b).
13b
Detaching and reinstalling the connectors
This is possible but not recommended.
Detaching and reinstalling the connectors (page
13a
Frame
L1, L2, L3,
size
T1/U, T2/V,
T3/W
N·m
lbf·ft
R6
30
22
R7
40
30
R8
40
30
R9
70
52
200).
PE,
N·m
lbf·ft
9.8
7.2
9.8
7.2
9.8
7.2
9.8
7.2