Download Print this page
ABB ACS580 Series Supplement Installation Manual

ABB ACS580 Series Supplement Installation Manual

Enclosed drives
Hide thumbs Also See for ACS580 Series:

Advertisement

Quick Links

ACS580-0P
Supplement Installation Manual for ACS580-0P
ACS580-0P Enclosed Drives (230V, 1-100 HP; 480V, 1-200 HP;
575, 2-150 HP)

Advertisement

loading

Summary of Contents for ABB ACS580 Series

  • Page 1 ACS580-0P Supplement Installation Manual for ACS580-0P ACS580-0P Enclosed Drives (230V, 1-100 HP; 480V, 1-200 HP; 575, 2-150 HP)
  • Page 3: Safety Instructions

    Supplemental Installation Manual for ACS580-0P Safety instructions These are the safety instructions which you • Handle the drive carefully. must obey when you install and operate the • Frames R5…R9: Lift the drive with a drive and do maintenance on the drive. If you lifting device.
  • Page 4: Electrical Safety In Installation, Start-Up And Maintenance

    Supplemental Installation Manual for ACS580-0P stop key on the control panel will not stop (3AXD50000044794) and Quick Start Guide (3AXD50000049129) for more information. the drive. • Before you connect voltage to the drive, • Frames R1…R5: Do not attempt to repair a make sure that the drive covers are on.
  • Page 5 Supplemental Installation Manual for ACS580-0P 5. Measure that the installation is Note: For other systems, connecting the de-energized. internal EMC filter will reduce the conducted emission. • Use a multimeter with an impedance of at • If the drive will be connected on a corner- least 1 Mohm.
  • Page 6 Supplemental Installation Manual for ACS580-0P The boards contain components sensitive to • install a device which automatically electrostatic discharge. disconnects the supply if the protective earth conductor breaks. Grounding These instructions are for all personnel who are responsible for the electrical installation, including the grounding of the drive.
  • Page 7: Additional Instructions For Permanent Magnet Motor Drives

    Supplemental Installation Manual for ACS580-0P Additional instructions for • Install temporary grounding to the drive output terminals (T1/U, T2/V, T3/W). permanent magnet motor drives Connect the output terminals together as well as to the PE. Safety in installation, start-up and Start-up and operation: maintenance •...
  • Page 8 ABB and its affiliates are not liable for damages and/or losses related to such security breaches, any unauthorized access, interference, intrusion, leakage and/or theft of data or information.
  • Page 9 Made in USA of Foreign Parts Input U1 3ph 400/480 VAC I1 52 A E211945 F1 50/60 Hz FRAME Output ABB Oy U2 3ph 0...U1 Hiomotie 13 I2 52 A 00380, Helsinki f2 0...500 Hz Finland Air cooling IP21...
  • Page 10: Installation

    Supplemental Installation Manual for ACS580-0P ACS580-0P Installation This information is unique to ACS580 input disconnect configurations (0P or 0P+F255). The ACS580 with Input Disconnect is an ACS580 AC adjustable frequency drive packaged with an input disconnect switch or circuit breaker. Refer to instructions on page 8, for all other information.
  • Page 11 Supplemental Installation Manual for ACS580-0P Connection diagrams – Vertical Packaged Drive with input disconnect ACS580-0P Vertical Packaged Drive units are configured for wiring access from the bottom only. The following figures show the layout and wiring connection points. For drive control wiring see . Maintain appropriate separation of control and power wires. ACS580 Drive Motor...
  • Page 12 Supplemental Installation Manual for ACS580-0P ACS580 Drive Motor Terminals Motor Ground Lug Fuses Disconnect Switch or Circuit Breaker Input Terminals Input Ground Lug P3/P4 (Px1-3, Px12-3, Px1-4, Px12-4) ACS580-0P...
  • Page 13 Supplemental Installation Manual for ACS580-0P Connection diagrams – Box Packaged Drive with input disconnect ACH580 Vertical Packaged Drive units are configured for wiring access from the top (for UL (NEMA) Type 1 and 12) and from the bottom (for UL (NEMA) Type 3R). The following figures show the layout and wiring connection points.
  • Page 14 Supplemental Installation Manual for ACS580-0P RHTR Temperature Heater ON Heater OFF HI/LO Jumper (X1) Temperature Temperature Default Setting 14.4 °C 21.4 °C (X1 jumper in LO 58 °F 70.5 °F position) Alternate Setting 17.8 °C 24.4 °C (X1 jumper in HI 64 °F 76.5 °F position)
  • Page 15 Supplemental Installation Manual for ACS580-0P Power connection terminals The following tables show maximum wire size and required tightening torque for incoming power, grounding and motor terminals. 1)“0P” represents disconnect and +F255 option code replaces the disconnect with a circuit breaker. Output 208/230 Volt Maximum Power Wiring Data...
  • Page 16 Supplemental Installation Manual for ACS580-0P Output 460 Volt Maximum Power Wiring Data Ratings Circuit Base Ground Breaker Circuit Disconnect Drive Disconnec Lugs (+F255) Breaker Switch Frame t Switch Motor Type Code Size UL (NEMA) Terminals UL (NEMA) (NEMA) (NEMA) (NEMA) Type 1 Type 3R Type 1...
  • Page 17 Supplemental Installation Manual for ACS580-0P 575 Volt Output Range Maximum Power Wiring Data Circuit Base Breaker Ground Drive Circuit Disconnect Disconnect (+F255) Lugs Frame Breaker UL Switch UL Switch Motor 1, 2 Type Code UL (NEMA) Size (NEMA) (NEMA) Type UL (NEMA) Terminals (NEMA)
  • Page 18 Supplemental Installation Manual for ACS580-0P Branch circuit protection Input power is connected to the ACS580 through a door interlocked disconnect switch or circuit breaker. When connected to a 240V or 480V power source, the ACS580 with the circuit breaker option is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes.
  • Page 19 Supplemental Installation Manual for ACS580-0P 460 Volt fuses for packaged drive Nominal Output 480 Volt Range Internal Drive External Fuse for Base Fuse Rating Disconnect Option Drive Package Drive Current Power Frame Type Code Size Current Max Current Class Class Rating Rating ACS580-0P-02A1-4...
  • Page 20 Supplemental Installation Manual for ACS580-0P Nominal Output 575 Volt Range Internal Drive External Fuse for Base Fuse Rating Disconnect Option Drive Package Drive Current Power Frame 1, 2 Type Code Size Current Max Current Class Class Rating Rating ACH580-PxR-052A-6 Class T ACH580-PxR-062A-6 Class T ACH580-PxR-077A-6...
  • Page 21: Operation

    Supplemental Installation Manual for ACS580-0P Operation This information is unique to ACS580 input disconnect configurations (0P). Refer to instructions on page for all other information. Operation Input disconnect configuration The ACS580 with Input Disconnect is an ACS580 AC adjustable frequency drive packaged with an input disconnect switch or circuit breaker, and with a door interlocked, external operating handle.
  • Page 22 Supplemental Installation Manual for ACS580-0P Dimensions P1 Type 1 ACS580-0P...
  • Page 23 Supplemental Installation Manual for ACS580-0P P1 Type 12 ACS580-0P...
  • Page 24 Supplemental Installation Manual for ACS580-0P P2 Type 1 ACS580-0P...
  • Page 25 Supplemental Installation Manual for ACS580-0P P2 Type 12 ACS580-0P...
  • Page 26 Supplemental Installation Manual for ACS580-0P P3 Type 1 ACS580-0P...
  • Page 27 Supplemental Installation Manual for ACS580-0P P3 Type 12 ACS580-0P...
  • Page 28 Supplemental Installation Manual for ACS580-0P P4 Type 1 ACS580-0P...
  • Page 29 Supplemental Installation Manual for ACS580-0P P4 Type 12 ACS580-0P...
  • Page 30 Supplemental Installation Manual for ACS580-0P PB1 Type 3R ACS580-0P...
  • Page 31 Supplemental Installation Manual for ACS580-0P PB2 Type 3R ACS580-0P...
  • Page 32 Supplemental Installation Manual for ACS580-0P PB3 Type 1 ACS580-0P...
  • Page 33 Supplemental Installation Manual for ACS580-0P PB3 Type 12 ACS580-0P...
  • Page 34 Supplemental Installation Manual for ACS580-0P [Page intentionally left blank] ACS580-0P...
  • Page 36 ABB Inc. 16250 West Glendale Drive New Berlin, WI 53151 Telephone +1 800 752-0696 +1 262 785-0397 Internet www.abb.com/drives...