Validating the operation of the Safe torque off function

See chapter
The Safe torque off function (page

Compliance with the EN 61800-3:2004 + A1:2012

Definitions

EMC stands for Electromagnetic Compatibility. It is the ability of
electrical/electronic equipment to operate without problems within an
electromagnetic environment. Likewise, the equipment must not disturb or
interfere with any other product or system within its locality.
First environment includes establishments connected to a low-voltage network
which supplies buildings used for domestic purposes.
Second environment includes establishments connected to a network not supplying
domestic premises.
Drive of category C1: drive of rated voltage less than 1000 V and intended for use
in the first environment.
Drive of category C2: drive of rated voltage less than 1000 V and intended to be
installed and started up only by a professional when used in the first environment.
Note: A professional is a person or organization having necessary skills in installing
and/or starting up power drive systems, including their EMC aspects.
Drive of category C3: drive of rated voltage less than 1000 V and intended for use
in the second environment and not intended for use in the first environment.
Drive of category C4: drive of rated voltage equal to or above 1000 V, or rated
current equal to or above 400 A, or intended for use in complex systems in the
second environment.

Category C1

The emission limits are complied with the following provisions:
1.
The optional EMC C1 filter is selected according to the documentation and
installed as specified in the EMC C1 filter manual. See
filter options (+F278, +F316, +E223) installation supplement for ACS580-01,
ACH580-01 and ACQ580-01 frames R1 to R5 (3AXD50000155132
Only available for IP55 (+B056) frames R1...R5, up to 55 kW.
2. The motor and control cables are selected as specified in this manual.
3. The drive is installed according to the instructions given in this manual.
4. The maximum motor cable length with 2 kHz switching frequency is 10 m.
Technical data 357
409).
Main switch and EMC C1
[Multilingual]).