Parameter
15.07 RO4 source
15.08 RO4 ON delay
15.09 RO4 OFF delay
Parameter setting example for digital output
This example shows how to make digital output DO1 of the extension module
indicate the reverse direction of rotation of the motor with a one-second delay.
Parameter
15.22 DO1 configuration
15.23 DO1 source
15.24 DO1 ON delay
15.25 DO1 OFF delay
Parameter setting example for frequency output
This example shows how to make digital output DO1 of the extension module
indicate the motor speed 0...1500 rpm with a frequency range of 0...10000 Hz.
Parameter
15.22 DO1 configuration
15.33 Freq out 1 source
15.34 Freq out 1 src min
15.35 Freq out 1 src max
15.36 Freq out 1 at src min
15.37 Freq out 1 at src max
Diagnostics
Faults and warning messages
Warning A7AB Extension I/O configuration failure.
LEDs
The extension module has one diagnostic LED.
Optional I/O extension and adapter modules 451
Setting
Reverse
1 s
1 s
Setting
Digital output
Reverse
1 s
1 s
Setting
Frequency output
01.01 Motor speed used
0
1500.00
0 Hz
10000 Hz