Cabinet Requirements for an EX4600 Switch

* Optics, Fans and Power supply sold separately for EX4600-40F-S.
40
Ensure that the rack complies with the standards for a 19-in. or 23-in. rack as defined in Cabinets,
Racks, Panels, and Associated Equipment (document number EIA-310–D) published by the Electronics
Industry Association.
A 600-mm rack as defined in the four-part Equipment Engineering (EE); European telecommunications
standard for equipment practice (document numbers ETS 300 119-1 through 119-4) published by
the European Telecommunications Standards Institute
href="http://www.etsi.org">http://www.etsi.org
(
The horizontal spacing between the rails in a rack that complies with this standard is usually wider
than the device's mounting brackets, which measure 19 in. (48.26 cm) from outer edge to outer
edge. Use approved wing devices to narrow the opening between the rails as required.
Ensure that the rack rails are spaced widely enough to accommodate the switch chassis' external
dimensions. The outer edges of the front-mounting brackets extend the width to 19 in. (48.26 cm).
The front and rear rack rails must be spaced between 28 in. (71.1 cm) and 36 in. (91.4 cm)
front-to-back.
The rack must be strong enough to support the weight of the switch.
Ensure that the spacing of rails and adjacent racks allows for proper clearance around the switch
and rack.
Secure the rack to the building structure.
If earthquakes are a possibility in your geographical area, secure the rack to the floor.
Secure the rack to the ceiling brackets as well as wall or floor brackets for maximum stability.
Chassis Physical Specifications for a EX4600 Switch on page 9
Rack-Mounting and Cabinet-Mounting Warnings on page 108

Clearance Requirements for Airflow and Hardware Maintenance for an EX4600 Switch

on page 41
Mounting an EX4600 Switch in a Rack or Cabinet on page 141
You can mount the EX4600 switch in a cabinet that contains a four-post 19-in. rack as
defined in Cabinets, Racks, Panels, and Associated Equipment (document number
EIA-310-D) published by the Electronics Industry Association.
Cabinet requirements consist of:
Cabinet size and clearance
Cabinet airflow requirements
Table 15 on page 41
provides the cabinet requirements and specifications for the EX4600

switch.

).