Closed-Loop Connector Sizes (Jis C 2805) (For 200 V/400 V Classes) - YASKAWA VARISPEED-616G5 Instruction Manual

200v class 0.4 to 75kw (1.2 to 110kva) 400v class 0.4 to 300kw (1.4 to 460kva)
Hide thumbs Also See for VARISPEED-616G5:
Table of Contents

Advertisement

Wiring
3.4.1 Applicable Wire Sizes and Closed-loop Connectors
3
IMPORTANT
Table 3.3

Closed-loop Connector Sizes (JIS C 2805) (For 200 V/400 V Classes)

2
Wire Thickness mm
0.5
0 5
0.75
0 75
1.25
1 25
2
3.5/5.5
3 5/5 5
8
14
14
22
22
30/38
50/60
50/60
80
100
100
150
200
325
325
Determine the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage.
Line voltage drop is calculated as follows:
(If there is the possibility of excessive voltage drop, use a larger wire suitable to the required length.)
Line voltage drop (V) = 3  x wire resistance (Ω/km) x wire length (m) x current (A) x 10
Terminal Screws
M3.5
M4
M3.5
M4
M3.5
M4
M3.5
M4
M5
M6
M8
M4
M5
M6
M8
M5
M6
M8
M6
M8
M6
M8
M8
M8
M10
M10
M10
M12
M12
2
×
M16
3 - 8
Size
1.25 to 3.5
1.25 to 4
1.25 to 3.5
1.25 to 4
1.25 to 3.5
1.25 to 4
2 to 3.5
2 to 4
2 to 5
2 to 6
2 to 8
5.5 to 4
5.5 to 5
5.5 to 6
5.5 to 8
8 to 5
8 to 6
8 to 8
14 to 6
14 to 8
22 to 6
22 to 8
38 to 8
60 to 8
60 to 10
80 to 10
100 to 10
100 to 12
150 to 12
200 to 12
325 to 12
325 to 16
−3