Setting Input Voltage; Input Voltage: E1-01; Setting The Power Supply Voltage Jumper - YASKAWA VARISPEED-616G5 Instruction Manual

200v class 0.4 to 75kw (1.2 to 110kva) 400v class 0.4 to 300kw (1.4 to 460kva)
Hide thumbs Also See for VARISPEED-616G5:
Table of Contents

Advertisement

5.2.4 Setting Input Voltage

Set the input voltage of the Inverter (E1-01) according to the power supply voltage.

Input Voltage: E1-01

J
Set the input voltage.
User
User
Constant
Number
E1-01
Input voltage setting
*
Values in parentheses are for 400 V class Inverters.
Use the following procedure to set a 200 V class Inverter to an input voltage of 230 V.
Step
Key Sequence
1
2
3
Press 10 times.
4
5
6
Press 3 times.
7
8
Setting the Power Supply Voltage Jumper (400 V Class Inverters of 18.5 kW or
J
Higher)
Set the power supply voltage jumper after setting the input voltage constant (E1-01) for 400 V class Invert-
ers of 18.5 kW or higher. Insert the jumper into the power tap nearest to the actual power supply voltage.
The jumper is factory-set to 440 V when shipped. If the power supply voltage is not 440 V, use the follow-
ing procedure to change the setting.
1. Turn OFF the power supply switch and wait for at least one minute (three minutes for models larger
than 30 kW) before removing the front panel and setting the jumper.
2. Remove the front cover.
3. Insert the jumper at the position for the voltage supplied to the Inverter (see Figure 5.1).
Change
g
during
during
Name
Opera-
tion
155 to 255
×
(310 to 510)*
Digital Operator Display
Main Menu
:
Initialize
Main Menu
:
Programming
Frequency Ref
DATA
ENTER
Terminal
Input Voltage
E1-01 = 200 VAC
Input Voltage
DATA
ENTER
200 VAC
Input Voltage
RESET
200 VAC
Input Voltage
230 VAC
DATA
ENTER
Entry Accepted
Input Voltage
E1-01 = 230 VAC
Main Menu
:
ESC
Programming
5 - 5
5.2 Trial Operation Procedures
Setting
Setting
Unit Factory
Factory
V/f
Range
Setting
Control
200
VAC
Q
(400)*
Displays initialize mode.
:
Displays programming mode.
:
Puts the Unit in programming mode.
Displays the input voltage setting dis-
play.
The leading digit will blink
The 2nd digit will blink.
Set to "3"
The set value is overwritten. "Entry
Accepted" is displayed for approxi-
mately 0.5 seconds.
Returns to the input voltage display.
Check that the data has been updated.
Returns to the programming mode
:
display.
Valid Access Levels
Open
V/f with
Flux
Loop
PG
Vector
Vector
Q
Q
Q
Remarks
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents