6.3.2 V/f Pattern Selection: E1-03

6.3.2 V/f Pattern Selection: E1-03
6
User
User
Constant
Name
Number
E1-03
V/f pattern selection
The V/f pattern can be set to any of the following:
D
One of 15 preset patterns (settings 0 through E)
A custom user-set pattern (setting F)
The factory setting for E1-03 is "F" (user-defined V/f pattern), but the default contents of this setting
D
are the same as setting "1."
Selecting a Preset V/f Pattern: E1-03 = "0" through "E"
J
Refer to the following table to set one of the 15 preset patterns.
D
Characteristics
These patterns are for general-purpose
applications
applications.
Use these patterns when the load torque
Use these patterns when the load torque
Fixed torque
Fixed torque
is to remain constant for any rotational
speed, such as in straight-line convey-
speed such as in straight-line convey-
ors.
Use these patterns when there is a qua-
U
dratic or cubic relationship between the
dratic or cubic relationship between the
Variable torque
Variable torque
rotational speed and load, such as in
fans or pumps.
fans or pumps
Select a high starting torque V/f pattern
only in the following cases:
S The wiring distance between the In
S The wiring distance between the In-
High starting
High starting
S A large torque is required at startup
S A large torque is required at startup
torque*
S An AC or DC reactor is connected to
S A motor less than the maximum appli-
These patterns are for applications that
These patterns are for applications that
High-speed op-
must rotate at frequencies greater than
eration
eration
60 Hz. A fixed voltage is applied at fre-
60 Hz. A fixed voltage is applied at fre-
quencies greater than 60 Hz.
*
Normally it isn't necessary to use these patterns because starting torque is ensured by auto-
matic torque boost functions.
The constant settings for E1-04 through E1-10 will be changed automatically when one of these pat-
D
terns is selected. There are three possible settings for these constants depending on the Inverter's ca-
pacity:
A 0.4 to 1.5 kW V/f pattern
A 2.2 to 45 kW V/f pattern
A 55 to 300 kW V/f pattern
The characteristics for these patterns are shown in the diagrams on the following pages.
D
Change
g
during
during
Setting
Setting
Opera-
Range
tion
0 to F
×
Applications
th
tt
h
th
i
verter and motor is relatively large
(greater than 150 m).
(such as for heavy axis loads).
the Inverter's input or output
the Inverter's input or output.
cable motor is being used.
6 - 22
Valid Access Levels
Unit Factory
Factory
V/f
V/f with
Setting
Control
PG
F
Q
Q
Setting
Specifications
0
50 Hz
1
60 Hz
2
60 Hz, Voltage saturation at 50 Hz
3
72 Hz, Voltage saturation at 60 Hz
4
50 Hz, cubic
5
50 Hz, quadratic
6
60 Hz, cubic
7
60 Hz, quadratic
8
50 Hz, low starting torque
9
50 Hz, high starting torque
A
60 Hz, low starting torque
b
60 Hz, high starting torque
C
90 Hz, Voltage saturation at 60 Hz
d
120 Hz, Voltage saturation at 60 Hz
E
180 Hz, Voltage saturation at 60 Hz
Open
Flux
Loop
Vector