Switching To V/F Control When Autotuning Is Not Successful; Open-Loop Vector Control - YASKAWA VARISPEED-616G5 Instruction Manual

200v class 0.4 to 75kw (1.2 to 110kva) 400v class 0.4 to 300kw (1.4 to 460kva)
Hide thumbs Also See for VARISPEED-616G5:
Table of Contents

Advertisement

Trial Operation
5.2.5 Autotuning
Display Message
Accelerate
PG Direction
Motor speed
ALARM: Over Load
(Displayed after completion of
autotuning)
Tune Aborted
Minor Fault:
VVV
V/f Over Setting
V/f Over Setting
5
Fault
Acceleration fault
Motor direction fault
Motor speed fault
Tuning overload fault
Minor fault
V/f setting exceeded
V/f setting exceeded
Fault displays can be cleared by pressing the MENU Key.
D
All set constants (motor constants) will be initialized if a fault occurs. Reset the constants from the
D
beginning when before starting autotuning again.
Inverter software Nos. VSG101020 to VSG101026 will display "ALARM: Over Load" when the
D
torque command exceeds 100%.

Switching to V/f Control when Autotuning Is Not Successful

J
When autotuning has not been executed correctly (i.e., when "Tune Aborted" is displayed), switch the con-
trol method to "V/f control" and set the V/f pattern.
1. Change the control method to V/f control without PG.
Step
Key Sequence
1
MENU
2
3
DATA
ENTER
4
Press twice.
5
DATA
ENTER
6
Press twice.
7
DATA
ENTER
8
MENU
Description
The motor did not accelerate with-
in a set time.
There is a contact fault between
the Inverter, PG (phase A and B),
and motor (phases U, V, and W)
The torque reference was too large
(100%) during autotuning.
The torque reference was over
20% during autotuning.
A minor Inverter fault occurred.
The torque command exceeded
100%, and the no-load current ex-
100%, and the no-load current ex-
ceeded 70% of the motor's rated
current.
Digital Operator Display
G5: Main Menu :
Operation
: Main Menu :
Initialize
Select Language
English
Control Method
Open Loop Vector
A1-02 = 2 :::
Open Loop Vector
A1-02 = 0
V/f Control
Entry Accepted
Control Method
V/f Control
G5: Main Menu :
Operation
5 - 8
Countermeasure
S Increase the acceleration time (C1-01).
S Increase the torque limits (L7-01, -02) if
these have been decreased.
S Disconnect the motor from the machine if
it has been connected.
S Check the PG wiring.
S Check the motor wiring.
S Check the PG direction and constant
F1-05.
S Disconnect the motor from the machine if
it has been connected.
S Increase the acceleration time (C1-01).
S Check the input data (particularly the num-
ber of PG pulses).
Check the input data (particularly the num-
ber of PG pulses) if the motor is being auto-
tuned separately.
Check the minor fault indicated in the boxes
in the display shown at the left.
S Check and adjust settings if necessary.
Check and adjust settings if necessary.
S Remove the load from the motor.
Remarks
Displays operation mode.
Displays initialize mode.
Puts the Unit in initialize mode. (Se-
lect Language display)
The control method selection is dis-
played.
Control method selection (A1-02) is
displayed.
Selects V/f control.
The set values are overwritten.
Returns to the control method select
display.
Returns to the operation mode dis-
play.