Cumulative Operation Time Settings: O2-07, O2-08 - YASKAWA VARISPEED-616G5 Instruction Manual

200v class 0.4 to 75kw (1.2 to 110kva) 400v class 0.4 to 300kw (1.4 to 460kva)
Hide thumbs Also See for VARISPEED-616G5:
Table of Contents

Advertisement

7.5.7 Operator Constants: o
7
Settings
D
Setting
0
Disable Operator detection. (Continue operation when the Digital Operator is disconnected.)
Enable Operator detection. (Detect an OPR fault when the Digital Operator is disconnected,
1
stop the Inverter output, and operate the fault contact.)

Cumulative Operation Time Settings: o2-07, o2-08

User
User
Constant
Name
Number
Cumulative opera-
o2-07
tion time setting
Cumulative opera-
o2-08
tion time selection
Set the initial elapsed time in constant o2-07. The elapsed operating time will start from this value.
D
Constant o2-08 determines whether the elapsed operating time is the time that the Inverter is on or the
D
time that the Inverter is running.
Settings
D
Setting
0
Inverter power-on time. (Counts the elapsed time from start-up until power is turned off.)
1
Inverter running time. (Counts the elapsed time that there is an Inverter output.)
Function
Change
g
during
during
Setting
Setting
Unit Factory
Opera-
Range
tion
0 to 65535
h
×
0, 1
×
Function
7 - 100
Valid Access Levels
Factory
Open
V/f
V/f with
Setting
Loop
Control
PG
Vector
A
A
A
0
A
A
A
0
Flux
Vector
A
A