Setting The Zero-Speed Operation Constants; Stopping Method Selection: B1-03; Zero-Speed Operation: B1-05 And Minimum Output Frequency: E1-09; Minimum Output Frequency (Fmin): E1-09 - YASKAWA VARISPEED-616G5 Instruction Manual

200v class 0.4 to 75kw (1.2 to 110kva) 400v class 0.4 to 300kw (1.4 to 460kva)
Hide thumbs Also See for VARISPEED-616G5:
Table of Contents

Advertisement

Setting
6
7
* 1. Speed agreement conditions: The frequency reference and output frequency were entered
in the speed agree detection width set in L4−02.
* 2. Speed agreement conditions: The frequency reference and the (actual) motor speed based
on the PG feedback value were entered in the speed agree detevtion width set in L4−02.
F1-10 and F1-11 Settings
D
Constant F1-10 sets the PG speed deviation detection level as a percentage of the maximum output
frequency. Constant F1-11 sets the length of time in seconds that the difference between the motor
speed and reference speed must exceed the PG speed deviation detection level in order to detect a PG
speed deviation (DEV).

6.4.2 Setting the Zero-speed Operation Constants

With flux vector control, operation is possible even when the frequency reference is zero (below the
D
minimum output frequency).
Set the operation methods for the minimum output frequency.
D

Stopping Method Selection: b1-03

J
Set the stopping method used when a stop command is input.
D
User
User
Constant
Number
b1-03
Stopping method
selection
Settings
D
Setting
0
1
2
3

Zero-speed Operation: b1-05 and Minimum Output Frequency: E1-09

J
Set the operation method used when the frequency reference is below the minimum output frequency.
D
User
User
Constant
Number
Operation selection
b1-05
for setting of E1-09
or less
Settings
D
Setting
0
1
2
3

Minimum Output Frequency (FMIN): E1-09

Set the minimum output frequency according to the requirements of the application.
D
User
User
Constant
Number
Min. output frequen-
E1-09
cy
Emergency stop using the emergency−stop time (C1−09)*2
Continue Operation (Displays "DEV" and continues control )*2
Change
g
during
during
Setting
Setting
Name
Opera-
Range
tion
0 to 3
×
Deceleration to stop
Coast to stop
DC injection braking stop (This setting can't be made with flux vector control.)
Coast to stop with timer (This setting can't be made with flux vector control.)
Change
g
during
during
Setting
Setting
Name
Opera-
Range
tion
0 to 3
×
Operate according to the frequency reference. (E1-09 is invalid.)
Interrupt the output. (Coast when the frequency reference is below E1-09.)
Operate at E1-09 frequency. (Output the frequency set in E1-09.)
Zero-speed operation (Zero reference value when the frequency reference is below E1-09.)
Change
g
during
during
Setting
Setting
Name
Opera-
Range
tion
0.0 to 400.0
×
6 - 31
6.4 Flux Vector Control
Function
Valid Access Levels
Unit Factory
Factory
V/f
V/f with
Setting
Control
PG
Q
Q
0
Function
Valid Access Levels
Unit Factory
Factory
V/f
V/f with
Setting
Control
PG
0
×
×
Function
Valid Access Levels
Unit Factory
Factory
V/f
V/f with
Setting
Control
PG
Q
Q
Hz
0.0
Open
Flux
Loop
Vector
Vector
Q
Q
6
Open
Flux
Loop
Vector
Vector
A
×
Open
Flux
Loop
Vector
Vector
Q
A