Fault Reset (Setting: 14); Timing Chart For Up And Down Commands; Motor Switch Command (Motor 2 Selection, Setting: 16) - YASKAWA VARISPEED-616G5 Instruction Manual

200v class 0.4 to 75kw (1.2 to 110kva) 400v class 0.4 to 300kw (1.4 to 460kva)
Hide thumbs Also See for VARISPEED-616G5:
Table of Contents

Advertisement

Output frequency
Upper limit
Accelerates to
lower limit
Lower limit
Forward/Stop
Up command
Down command
Speed Agree signal
Power supply
The Speed Agree signal remains ON while the run command is ON and the motor is
not accelerating or decelerating.
Fig 7.36

Fault Reset (Setting: 14)

OFF
Normal operation
ON
Resets faults when input goes from OFF to ON. (Normal operation when no fault has occurred.)
With this setting, the multi-function input resets faults that have occurred.
D
When a fault has occurred, be sure to find out what kind of fault occurred, take steps to correct the cause
D
of the fault, and restart the Inverter. It is possible to damage the Inverter by repeatedly resetting a fault
without correcting the cause.
To resume operation after a fault has occurred, turn the run command OFF, turn the fault reset input
D
from ON to OFF, and then turn the run command ON again. A fault cannot be reset while the run com-
mand is ON.
If a fault hasn't occurred, turning the fault reset ON and OFF will have no effect on operation.
D

Motor Switch Command (Motor 2 Selection, Setting: 16)

CLOSED: Motor 2 constants used.
D
Operation
Motor Switch command
(CLOSED for motor 2)
The control method, V/f characteristics, and motor constants recorded in the Inverter can be
switched by setting "16" (motor switch command) for a constant from H1-01 to 06 (multi-function
inputs), and then inputting a signal while the motor is stopped.
ON
ON
Reference frequency reset
ON
ON
ON

Timing Chart for Up and Down Commands

Note Use an external sequence to switch between M1 and M2
and to confirm the motor selection status.
U, V, W
(T1, T2, T3)
Multi-function input
Multi-function output
7 - 69
d4-01=1
Same frequency
d4-01=0
ON
M1
IM
Motor 1 (main motor)
M2
Motor 2 (auxiliary motor)
IM
Motor selection monitor
(CLOSED for motor 2)
7