During Run (Setting: 0); During Run 2 (Setting: 37); Zero-Speed (Setting: 1); Timing Chart For Zero-Speed - YASKAWA VARISPEED-616G5 Instruction Manual

200v class 0.4 to 75kw (1.2 to 110kva) 400v class 0.4 to 300kw (1.4 to 460kva)
Hide thumbs Also See for VARISPEED-616G5:
Table of Contents

Advertisement

7.5.5 External Terminal Functions: H
7

During Run (Setting: 0)

OFF
The run command is OFF and there is not output voltage.
ON
The run command is ON or a voltage is being output.

During Run 2 (Setting: 37)

The Inverter is not outputting a frequency. (Baseblock, DC injection braking, initial excitation,
OFF
or stopped)
ON
The Inverter is outputting a frequency.
These outputs can be used to indicate the Inverter's operating status.
D
Run command
Baseblock command
Output frequency
During run 1 output
During run 2 output
Fig 7.43
Timing Chart for "During RUN" Output

Zero-speed (Setting: 1)

The output frequency is greater than the minimum output frequency (E1-09).
OFF
(With flux vector control, is greater than the zero speed level (b2-01).)
The output frequency is less than the minimum output frequency (E1-09).
ON
(With flux vector control, is less than the zero speed level (b2-01).)
Output frequency
Zero-speed output
OFF
Fig 7.44

Timing Chart for Zero-speed

Motor Overload (OL1) Pre-alarm (Setting: 1F)
OFF
The motor protection function's electronic thermal value is less than 90% of the detection level.
ON
The motor protection function's electronic thermal value is greater than 90% of the detection
level.
This output function is valid when the motor overload protection function is enabled (L1-01 =1).
D
This output can be used to warn of overheating before the protection function itself operates.
D
Inverter Overheat (OH) Pre-alarm (Setting: 20)
OFF
The cooling fin temperature is less than the "OH Pre-Alarm Level" set in L8-02.
ON
The cooling fin temperature exceeds the "OH Pre-Alarm Level" set in L8-02.
This output function indicates that the temperature of the cooling fins reaches the temperature set in
D
L8-02 (the Inverter overheating alarm detection level).
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Minimum output frequency (E1-09)
(Zero speed level (b2-01) when flux vector control is
being used.)
ON
7 - 78