Analog Monitor Card: F4-01 to F4-04

J
When using an AO-08 or AO-12 Analog Monitor Card, set the monitor items and gain with the follow-
D
ing constants.
User
User
Name
Constant
Number
Channel 1 monitor
F4-01
selection
F4-02
Channel 1 gain
Channel 2 monitor
F4-03
selection
F4-04
Channel 2 gain
Channel 1 output
F4-05
bias
Channel 2 output
F4-06
bias
Fig 7.33

Analog Output Block Diagram

For the output monitor selections (F4-01, F4-03), set the numbers for the right side of the "U1"
D
constants in the Table 4.3. The setting range is 1 to 38, but the following numbers cannot be set: 4, 10,
11, 12, 13, 14, 25, and 28 to 35.
When the AO-12 is used, outputs of 0 to ±10 V are possible. For that, set constant H4-07 (multi-func-
D
tion analog output signal level selection) to "1" (0 to ±10 V outputs). There are some monitor items.
However, that can only use outputs of 0 to +10 V even if constant H4-07 is set to "1."
When the AO-08 is used, only outputs of 0 to +10 V are possible regardless of the constant H4-07 set-
D
ting.

DO-02 Digital Output Card Settings: F5-01, F5-02

J
Set the output selections in the following constants when using a DO-02 Digital Output Card.
D
User
User
Constant
Name
Number
Channel 1 output
F5-01
selection
Channel 2 output
F5-02
selection
Set the values from Table 7.10.
D
Change
g
during
during
Setting
Setting
Opera-
Range
tion
1 to 38
×
0.00 to 2.50
f
1 to 38
×
0.00 to 2.50
f
−10.0 to
f
+10.0
−10.0 to
f
+10.0
+
F4-02
AO
(F4-04)
+
Output gain
F4-05
(F4-06)
Output bias
Change
g
during
during
Setting
Setting
Opera-
Range
tion
00 to 37
×
00 to 37
×
7 - 61
7.5 Common Functions
Valid Access Levels
Unit Factory
Factory
V/f
V/f with
Setting
Control
PG
2
B
B
Mul-
1.00
B
B
tiple
B
B
3
Mul-
0.50
B
B
tiple
B
B
%
0.0
%
0.0
B
B
Valid Access Levels
Unit Factory
Factory
V/f
V/f with
Setting
Control
PG
0
B
B
B
B
1
Open
Flux
Loop
Vector
Vector
B
B
B
B
B
B
B
B
B
B
B
B
7
Open
Flux
Loop
Vector
Vector
B
B
B
B