Hold Reference Memory Selection: D4-01; Trim Control Level: D4-02 - YASKAWA VARISPEED-616G5 Instruction Manual

200v class 0.4 to 75kw (1.2 to 110kva) 400v class 0.4 to 300kw (1.4 to 460kva)
Hide thumbs Also See for VARISPEED-616G5:
Table of Contents

Advertisement

Advanced Operation
7.5.3 Reference Constants: d
7
Internal frequency reference
d3-03
Fig 7.31
Setting Prohibited Frequencies

Hold Reference Memory Selection: d4-01

J
Constant d4-01 is enabled by making either of the following settings for the multi-function inputs
D
(H1-01 to H1-06).
Acceleration/deceleration ramp hold (setting: A)
Up command (setting: 10)/down command (setting: 11)
When hold status is established by these external signals, specify whether or not the output frequency
D
is to be retained.
When this function is enabled, operation is re-started after power-up using the frequency reference val-
D
ue that was retained.
User
User
Constant
Name
Number
Frequency reference
d4-01
hold function selec-
tion
Settings
D
Setting
0
Disabled. Restart after operation stoppage or power-up begins at zero.
1
Enabled. Restart after operation stoppage or power-up begins at the held frequency reference.
For information regarding the acceleration/deceleration stop (hold) command and the up/down com-
D
mand, refer to the description of Multi-function Inputs (H1).

Trim Control Level: d4-02

J
The trim control level is valid when the trim control increase command (setting: 1C) or trim control
D
decrease command (setting: 1D) is set for a multi-function input (H1-01 to H1-06).
If the trim control increase command is ON when a frequency reference is input on the analog input,
D
the trim control level will be added to the analog frequency reference and then output as the output
frequency. If the trim control decrease command is ON, the frequency reference will be decreased by
the trim control level.
User
User
Constant
Name
Number
d4-02
+ − Speed limits
Set the trim control level as a percentage of the maximum output frequency.
D
If the frequency reference minus the trim control level is less than zero, the output frequency will be
D
zero.
Refer to the description of Multi-function Inputs (H1) for details on the trim control increase and trim
D
control decrease commands.
d3-04
Dotted lines show operation during
acceleration/deceleration.
Set frequency reference
d3-02
d3-01
Change
g
during
during
Setting
Setting
Unit Factory
Opera-
Range
tion
0, 1
×
Description
Change
g
during
during
Setting
Setting
Unit Factory
Opera-
Range
tion
0 to 100
%
×
7 - 58
Valid Access Levels
Factory
Open
V/f
V/f with
Setting
Loop
Control
PG
Vector
0
A
A
A
Valid Access Levels
Factory
Open
V/f
V/f with
Setting
Loop
Control
PG
Vector
A
A
A
25
Flux
Vector
A
Flux
Vector
A