Wiring Main Circuit Terminals; Applicable Wire Sizes And Closed-Loop Connectors - YASKAWA Varispeed F7 Instruction Manual

Hide thumbs Also See for Varispeed F7:
Table of Contents

Advertisement

Wiring Main Circuit Terminals

Applicable Wire Sizes and Closed-loop Connectors

Select the appropriate wires and crimp terminals from Table 2.1 to Table 2.3. Refer to instruction manual
TOE-C726-2 for wire sizes for Braking Resistor Units and Braking Units.
Inverter
Model
CIMR-
F7A20P4
F7A20P7
F7A21P5
F7A22P2
F7A23P7
F7A25P5
F7A27P5
F7A2011
F7A2015
F7A2018
F7A2022
F7A2030
-6
2
Table 2.1 200 V Class Wire Sizes
Terminal Symbol
R/L1, S/L2, T/L3,
,
1,
2, B1, B2,
U/T1, V/T2, W/T3
R/L1, S/L2, T/L3,
,
1,
2, B1, B2,
U/T1, V/T2, W/T3
R/L1, S/L2, T/L3,
,
1,
2, B1, B2,
U/T1, V/T2, W/T3
R/L1, S/L2, T/L3,
,
1,
2, B1, B2,
U/T1, V/T2, W/T3
R/L1, S/L2, T/L3,
,
1,
2, B1, B2,
U/T1, V/T2, W/T3
R/L1, S/L2, T/L3,
,
1,
2, B1, B2,
U/T1, V/T2, W/T3
R/L1, S/L2, T/L3,
,
1,
2, B1, B2,
U/T1, V/T2, W/T3
R/L1, S/L2, T/L3,
,
1,
2, B1, B2,
U/T1, V/T2, W/T3
R/L1, S/L2, T/L3,
,
1,
2, U/T1, V/T2,
W/T3
B1, B2
R/L1, S/L2, T/L3,
,
1,
2, U/T1, V/T2,
W/T3
B1, B2
R/L1, S/L2, T/L3,
,
1, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31
3
R/L1, S/L2, T/L3,
,
1 U/T1,
V/T2, W/T3, R1/L11, S1/L21, T1/L31
3
Possible
Tightening
Termi-
Wire Sizes
Torque
nal
Screws
2
(N•m)
mm
(AWG)
2 to 5.5
M4
1.2 to 1.5
(14 to 10)
2 to 5.5
M4
1.2 to 1.5
(14 to 10)
2 to 5.5
M4
1.2 to 1.5
(14 to 10)
2 to 5.5
M4
1.2 to 1.5
(14 to 10)
3.5 to 5.5
M4
1.2 to 1.5
(12 to 10)
5.5
M4
1.2 to 1.5
(10)
8 to 14
M5
2.5
(8 to 6)
14 to 22
M5
2.5
(6 to 4)
30 to 38
M6
4.0 to 5.0
(4 to 2)
8 to 14
M5
2.5
(8 to 6)
22
M6
4.0 to 5.0
(4)
30 to 38
M8
9.0 to 10.0
(3 to 2)
8 to 14
M5
2.5
(8 to 6)
22
M6
4.0 to 5.0
(4)
30 to 60
M8
9.0 to 10.0
(3 to 1)
8 to 22
M6
4.0 to 5.0
(8 to 4)
22 to 38
M8
9.0 to 10.0
(4 to 2)
50 to 60
M8
9.0 to 10.0
(1 to 1/0)
8 to 22
M6
4.0 to 5.0
(8 to 4)
22 to 38
M8
9.0 to 10.0
(4 to 2)
Recom-
mended
Wire Size
Wire Type
2
mm
(AWG)
2
(14)
2
(14)
2
(14)
2
(14)
3.5
(12)
5.5
(10)
8
(8)
Power cables,
14
e.g., 600 V vinyl
(6)
power cables
30
(4)
-
22
(4)
30
(3)
-
22
(4)
30
(3)
-
22
(4)
50
(1)
-
22
(4)

Advertisement