MEMOBUS Communications Settings: H5-01 to H5-05
J
Station Node Address: H5-01
Set the Inverter node address.
D
User
User
Constant
Name
Number
H5-01
Station address
Baud Rate: H5-02
Set the baud rate for MEMOBUS communications.
D
User
User
Name
Constant
Number
H5-02
Communication
speed selection
Settings
D
Setting
0
1200 bps
1
2400 bps
2
4800 bps
3
9600 bps
4
19200 bps
Communication Parity: H5-03
Set the parity for MEMOBUS communications.
D
User
User
Name
Constant
Number
Communication par-
H5-03
ity selection
Settings
D
Setting
0
No parity
1
Even parity
2
Odd parity
Stopping Method after Communications Error: H5-04
Set the stopping method to used after a communications error is detected.
D
User
User
Constant
Name
Number
Stopping method af-
H5-04
ter communication
error
Settings
D
Setting
0
Deceleration to stop (deceleration time:C1-02)
1
Coast to stop
2
Emergency stop (deceleration time:C1-09)
3
Continue operation (display only)
Change
g
during
during
Setting
Setting
Unit Factory
Opera-
Range
tion
0 to 20
−
×
Change
g
Setting
Setting
Unit Factory
during
during
Range
Opera-
tion
0 to 4
−
×
Baud Rate
Change
g
during
during
Setting
Setting
Unit Factory
Opera-
Range
tion
0 to 2
−
×
Function
Change
g
during
during
Setting
Setting
Unit Factory
Opera-
Range
tion
0 to 3
−
×
Function
7 - 83
Valid Access Levels
Factory
Open
V/f
V/f with
Setting
Loop
Control
PG
Vector
A
A
A
1F
Valid Access Levels
Factory
Open
V/f
V/f with
Setting
Loop
Control
PG
Vector
3
A
A
A
Valid Access Levels
Factory
Open
V/f
V/f with
Setting
Loop
Control
PG
Vector
0
A
A
A
Valid Access Levels
Factory
Open
V/f
V/f with
Setting
Loop
Control
PG
Vector
3
A
A
A
Flux
Vector
A
Flux
Vector
A
Flux
Vector
A
7
Flux
Vector
A