4.2.7 Autotuning Mode

D Disconnect the load (machine, device) from the motor before autotuning.
EXAMPLE

Autotuning Procedure

A
"
The motor may turn, possibly resulting in injury or damage to equipment. Also, motor constants cannot be
correctly set with the motor attached to a load.
Autotuning automatically tunes and sets the required motor constants when operating in the open-loop or
flux vector control modes. Always perform autotuning before starting operation.
When the rated voltage, rated current, rated frequency, and number of poles listed on the motor nameplate
have been input and the RUN Key is pressed, the motor constants calculated from these values will be writ-
ten to E1-04 through E2-09 automatically.
When the motor cannot be disconnected from the load, motor constants can be set by calculation. Contact
your Yaskawa representatives for details.
The autotuning mode won't be displayed if V/f control has been selected. Refer to Setting the Control
Method: A1-02 under 4.2.5 Initialize Mode.
The Inverter's autotuning function automatically determines the motor constants, while a servo system's
autotuning function determines the size of a load, so these autotuning functions are fundamentally differ-
ent.
Step
Key Sequence
1
MENU
2
press 3 times.
3
DATA
ENTER
4
DATA
ENTER
5
RESET
6
DATA
ENTER
7
8
DATA
DATA
ENTER
ENTER
RESET
9
10
DATA
DATA
ENTER
ENTER
RESET
11
12
DATA
DATA
ENTER
ENTER
RESET
CAUTION
Digital Operator Display
G5: Main Menu :
Operation
G5: Main Menu :
Autotuning
Rated Voltage
200.0 VAC
Rated Voltage
200.0 VAC
Rated Voltage
200.0 VAC
Entry Accepted
Rated Voltage
200.0 VAC
Rated Current
1.90 A
Rated Frequency
60.0 HZ
Rated Speed
1750 RPM
4 - 29
4.2 Modes
Remarks
The leading digit blinks.
When Increment Key is pressed,
blinking value increases. When
Decrement Key is pressed, blinking
value decreases.
The digit to be set moves to the right
and blinks. Follow the above proce-
dures as outlined in step 4.
After selecting values for steps 4 and
5, press DATA/ENTER Key.
The Operator display is as shown on
the left. The value is written-in.
After a few seconds, the Operator dis-
play is as shown on the left.
Press the keys as in steps 4, 5, 6 of
rated voltage setting.
Press the keys as in steps 4, 5, 6 of
rated voltage setting.
Press the keys as in steps 4, 5, 6 of
rated voltage setting.