Monitor Constants; Using The Analog Monitor Constants - YASKAWA Varispeed G7 Instruction Manual

General purpose inverter (advanced vector control)
Hide thumbs Also See for Varispeed G7:
Table of Contents

Advertisement

Monitor Constants

This section explains the analog monitor and pulse monitor constants.

Using the Analog Monitor Constants

This section explains the analog monitor constants.
Related Constants
Con-
stant
Number
H4-01
H4-02
H4-03
H4-04
H4-05
H4-06
-88
6
Name
Description
Display
Monitor selec-
Sets the number of the monitor
tion (terminal
item to be output (U1-
FM)
terminal FM.
4, 10 to 14, 25, 28, 34, 39, 40 can-
Terminal FM
not be set. 29 to 31 and 41 are not
Sel
used.
Gain (terminal
Sets the multi-function analog
FM)
output 1 voltage level gain.
Sets whether the monitor item
output will be output in multiples
of 10 V.
Terminal FM
The maximum output from the
Gain
terminal is 10 V. A meter calibra-
tion function is available.
Bias (terminal
Sets the multi-function analog
FM)
output 1 voltage level bias.
Sets output characteristic up/
down parallel movement as a per-
centage of 10 V.
Terminal FM
The maximum output from the
Bias
terminal is 10 V. A meter calibra-
tion function is available.
Monitor selec-
Sets the number of the monitor
tion (terminal
item to be output (U1-
AM)
terminal AM.
4, 10 to 14, 25, 28, 34, 39, 40 can-
Terminal AM
not be set. 29 to 31 and 41 are not
Sel
used.
Gain (terminal
Set the voltage level gain for
AM)
multi-function analog output 2.
Set the number of multiples of 10
V to be output as the 100% output
for the monitor items. The maxi-
Terminal AM
mum output from the terminal is
Gain
10 V. A meter calibration function
is available.
Bias (terminal
Sets the multi-function analog
AM)
output 2 voltage level bias.
Sets output characteristic up/
down parallel movement as a per-
centage of 10 V.
Terminal AM
The maximum output from the
Bias
terminal is 10 V. A meter calibra-
tion function is available.
Change
Setting
Factory
during
Range
Setting
Opera-
tion
) from
1 to 45
2
No
1 to 99
0.00 to
1.00
Yes
2.50
-10.0
to
0.0%
Yes
+10.0
) from
1 to 45
3
No
1 to 99
0.00 to
0.50
Yes
2.50
-10.0
to
0.0%
Yes
+10.0
Control Methods
Open
Open
V/f
Flux
Loop
Loop
V/f
with
Vec-
Vector
Vector
PG
tor
1
2
A
A
A
A
A
Q
Q
Q
Q
Q
A
A
A
A
A
A
A
A
A
A
Q
Q
Q
Q
Q
A
A
A
A
A
MEMO
BUS
Regis-
ter
41DH
41EH
41FH
420H
421H
422H