Chapter 7 Servo Parameters|ASDA-A&A+ Series
P4 - 15
COF1
Default: Factory setting
Applicable Control Mode: ALL
Unit: N/A
Range: 0~32767
Settings:
Manual Adjustment Operation:
Set parameter P2-08 to 22 and then change this parameter. This is an auxiliary adjusting
function, although this parameter allows the users can execute manual adjustment, we still do
not recommend users to change the default setting manually.
Auto Adjustment Operation:
Set parameter P2-08 to 20 first and then set parameter P4-10 to 3. When executing this auto
adjustment, please short the internal circuit of the analog input voltage first or connecting to a 0V
output of the external controller in advance and make sure that the status of the servo drive is
"Servo Off" and the servo motor has stopped.
1) When P2-08 is set to 10, users cannot reset this parameter.
P4 - 16
COF2
Default: Factory setting
Applicable Control Mode: ALL
Unit: N/A
Range: 0~32767
Settings:
Please see P4-15 for explanation.
1) When P2-08 is set to 10, users cannot reset this parameter.
7-86
Call 1(800)985-6929 for Sales
deltaacdrives.com
Current Detector Drift Adjustment (V1 phase)
NOTE
Current Detector Drift Adjustment (V2 phase)
NOTE
deltaacdrives.com
sales@deltaacdrives.com
Communication Addr.: 040FH
Related Section: N/A
Communication Addr.: 0410H
Related Section: N/A