Connecting AC Power

For North American installations, the AC Power Cord terminates on one end with a NEMA-15P plug
to connect to the AC mains socket-outlet at the wall. For installations in other regions, the plug to be
used must comply with the local regulations and be marked as such, be suitable for the current and
voltage being used and contain an earthing pin for connection to ground at the AC mains socket-
outlet through the cord.
To prevent accidental interruption of power to the G700 Media Gateway, do not connect the G700
Media Gateway to a switch-controlled AC wall socket-outlet. Avaya Inc. highly recommends that the
customer use a UPS for back-up power.
Advise your customer to verify through a licensed electrician that the ground connection at the AC
outlet to be used is attached to an approved ground.

Power Requirements

The G700 Media Gateway uses an auto-ranging 100-240 VAC power supply, 50 to 60 Hz, 5 A
maximum at 100-120 VAC and 2 A maximum at 200-240 VAC. The AC power source is to be single
phase, 3-conductor (Line, Neutral and Ground) with a 15 A circuit breaker for 100-120 VAC or a 10
A circuit breaker for 200-240 VAC.

Testing the AC Outlet

!
WARNING:
The following recommended test equipment, tests and diagrams are intended only for
North American installations at 110 to 125 Volts AC. For installations in other
regions, have a licensed electrician verify the ground and voltages.
!
WARNING:
If the AC outlet tests indicate that the power requirements are not met, your customer
must contact a licensed electrician. DO NOT install the system until all requirements
are met.
Fault Conditions
If the AC outlet tests that follow reveal any of the following conditions, they must be corrected
BEFORE the system is to be installed.
• Open ground
• Hot and neutral reversed
• Open hot
• Open neutral
• Hot and ground reversed
!
WARNING:
Hazardous voltages are present during this test. Follow all instructions carefully
when working the AC power line voltages.
Installation and Upgrades for G700
555-234-100 – Issue 1 – May 2002
2 G700 Media Gateway: Attaching Ground Conductors