3.11.3. Compax3M Sto Application Description; Sto Function With Safety Control Device Via Compax3M Inputs; Sto Function Description - Parker Compax3 Series Operating Instructions Manual

Electromechanical automation, positioning via devicenet
Hide thumbs Also See for Compax3 Series:
Table of Contents

Advertisement

Parker EME

3.11.3. Compax3M STO application description

In this chapter you can read about:

STO function with safety control device via Compax3M inputs..........................................93

STO function description ....................................................................................................93

STO function with safety switching device for applications with fieldbusses......................95
Emergency power-off and protective door monitoring without safety switching devices....97
3.11.3.1
3.11.3.2
STO function with safety control device via Compax3M inputs
Compax3M
Compax3M
*
Not-Aus
Emergency
switch off
The acknowledement via the safety control UE410-MU3T5 is only necessary, if
after the disabling of the STO function, a danger to any person or to the machine
could arise. During the Configuration des Compax3M (see page 132)you must
see to a debouncing time >3ms being configured.
The operating instructions of the UE410-MU3T5 safety control must be observed.
The Compax3M devices and the UE410-MU3T5 safety control must be mounted in
the same control cabinet.
STO function description
When opening the protective door or after actuating the emergency power-off
switch, the singal of the "energize" input of the Compax3M drive modules is inter-
192-120114 N5 C3I22T11 June 2008
X3
Quit
Energize
X14.1
X14.2
X14.3
X14.4
X3
Quit
Energize
X14.1
X14.2
X14.3
X14.4
S1
I4
A2
GND24V
A1
S3
EN
S2
Quit
+24V
Compax3 device description
motor
Gefahrenbereich
Danger Zone
motor
Schutztür offen
Safety door open
S1
S2
*
I3
I2
I1
X1
X2
UE410-MU3T5
Delay
Time
Q1
Q2
Q3
Q4