Devicenet Connector X23 - Parker Compax3 Series Operating Instructions Manual

Electromechanical automation, positioning via devicenet
Hide thumbs Also See for Compax3 Series:
Table of Contents

Advertisement

Parker EME
3.7.3.

DeviceNet connector X23

3.7.3.1
Pin X23
DeviceNet (Open Plug Phoenix MSTB 2.5/5-GF5.08 ABGY AU)
1
V-
2
CAN-
3
Shield
4
CAN+
5
V+
A mating plug is included in the delivery.
If Compax3 is used as first or last device in the fieldbus network, a terminal resi-
stance of 121 Ω is required. This is integrated between Pin 2 and Pin 4.
Additional information on the DeviceNet wiring can be found under www.odva.org
http://www.odva.org.
Please do also heed the instructions in the DeviceNet master manual.
Adjusting the bus address
Address setting (NA: Node Address)
Values:
1: 2
; 2: 2
; 3: 2
; ... 6: 2
0
1
2
5
Settings:
left: OFF
right: ON
(The address is set to 2 in the illustration)
Range of values: 1 ... 63
Address 0 is set internally to address 63.
Data Rate setting (DR):
Data Rate [kBit/s]
S24_7
125
left: OFF
250
left: ON
500
right: OFF
Reserved
right: ON
Bear in mind that the maximum cable length depends on the Data rate:
Data Rate
Maximum length
500kbit/s
100m
250kbit/s
250m
125kbit/s
500m
192-120114 N5 C3I22T11 June 2008
Mass
CAN Low
Shield
CAN High
not required, internal supply
reserved
S24_8
left: OFF
right: OFF
left: ON
right: ON
Compax3 device description