3.5.5.

Control voltage 24VDC Compax3MP (mains module)

3.5.6.
Mains supply Compax3MP (mains module)
Device protection
connector X9
PIN
Designation
1
+24V
2
Gnd 24 V
Control voltage 24VDC Compax3MP / Compax3M
Device type
Voltage range
Mains module
Fuse
Current drain of the device
Total current drain
Ripple
Requirement according to safe extra
low voltage (SELV)
Short-circuit proof
By cyclically switching on and off the power voltage, the input current limita-
tion can be overloaded, which may cause damage to the device.
Wait at least one minute between two switching on processes!
Connector X41
Pin designation
PE
L3
L2
L1
192-120114 N5 C3I22T11 June 2008
Line cross sections:
minimum: 0.5mm
with contactor sleeve
2
maximum: 6mm
with contactor sleeve
2
(AWG: 20 ... 10)
Compax3MP / Compax3M
21 - 27VDC
with switch-on current limitation, due to capaci-
tive load
MCB miniature circuit breaker or "delayed ac-
tion fuse", due to capacitive load
C3MP10D6: 0.2A
C3MP20D6: 0.3A
C3M050D6: 0.85A
C3M100D6: 0.85A
C3M150D6: 0.85A
C3M300D6: 1.0A
+ Total load of the digital outputs + current for
the motor holding brake
0.5Vpp
yes
conditional (internally protected with 3.15AT)
Compax3 device description
45