6-2-1-7. Manual Reset Mode with Reset Switch Connector

[Wiring Example]
F39-JG†C-L
S1
Function
EDM
Interlock *6
Operating Range Selection
Non-Muting system
External Test used
Optical Synchronization
Timing chart
Beam state: Unblocked
Blocked
Test switch (S1)
Reset switch (S2)
OSSD
• When using the Reset Switch Connector (F39-GCNY3), the following functions are not available.
- External Device Monitoring (EDM)
• When a functional earth is necessary, wire an earth cable according to the example in 6-2-1-1. Auto Reset Mode with
Optical Synchronization and EDM Unused. Also refer to 5-4-4. Functional Earth Connection for more information.
F3SG-SR
322
User's Manual
XS5F-D421†80-F
L1
S2
DIP switch
EDM Disabled (factory default setting)
Manual Reset
Long : Open the OPERATING RANGE SELECT INPUT line of the emitter or connect the line to 24 VDC.
Long *6
Perform wiring according to the wiring diagram.
N/A
Connect the TEST line of the emitter to 24V/0V of the emitter via a test switch (NO contact). *7
N/A
Open the COM(+) and COM(-) lines of the emitter.
S1: Test switch
S2: Lockout/interlock reset switch
L1: Lamp
*1. Reverse the polarity of the power supply when using in the NPN system.
*2. Connect the line to 0 VDC if Operating Range Selection is used in Short
*3. Refer to 6-3. Connectable Safety Control Units for more information.
*4. The safety controller and the F3SG-SR must share the power supply or be
*5. This is the case for a PELV circuit.
*6. Set the function with the DIP Switches on the Intelligent Tap or the SD
*7. This wiring example shows light emission stop when connected to 24 VDC
F39-JGR3K-D
F39-GCNY3
F39-JG†A-D
*5
IN1
IN2
Safety controller
*3 *4
Setting
[Start interlock] : Enable
[Restart interlock] : Enable
[Operating Range Selection] : Long mode *6
[Muting] : Disable *6
[External test signal inversion] : Disable
Select a safety controller of PNP or NPN type according to the system of
your application.
Mode.
connected to the common terminal of the power supply.
Manager 3, restore the settings to the F3SG-SR, and perform wiring
according to the wiring diagram.
with PNP setting, and light emission stop when connected to 0 VDC with
NPN setting. If TEST switch is not needed, refer to 2-6. External Test.
Intelligent Tap
Needed
Wiring for NPN *1
24 VDC
24 VDC
: Indicates a switch position.
SD Manager 3

Advertisement