2-14-5. Setting with SD Manager 3
The user can make changes to the settings of this function by the SD Manager 3.
Function
Override
Override input time limit
Override time limit
It is recommended that the Position 2 of the DIP Switch be set at OFF (DIP Switch Disabled).
Setting the override time limit to infinite may cause a failure of disabling the OVERRIDE state when there is a failure of
the override input signal. Conduct risk assessment analysis thoroughly before enabling this setting.
Refer to Chapter 4 Setting with SD Manager 3 for more information on setting this function by the SD Manager 3.
Initial value
Enable
1 s
600 s
System Operation and Functions
Configurable value or numerical range
Enable/Disable
0.2 to 5 s in 0.1-s increments
1 to 600 s in 1-s increments, or infinite
E
F3SG-SR
89
User's Manual