2. Functions, Wiring and Settings
2-3 Reset Mode
Set the reset mode using feedback/reset input terminals T31, T32, and T33.
Reset mode
Auto reset mode
Manual reset mode
G9SX
62
USER'S GUIDE
Wiring
Feedback Loop
KM1
KM2
KM3
KM4
+24 V
KM5
T31
T32
T33
Feedback Loop
KM1
Reset
KM2
switch
KM3
KM4
+24 V
KM5
T31
T32
T33
Function summary
The signal to terminal T33 must be ON for the
safety output to turn ON.
If terminal T33 is not ON, the safety output will
not turn ON.
The signal to terminal T32 must turn ON and then
OFF for the safety output to turn ON.
If terminal T32 does not turn ON and then OFF,
the safety output will not turn ON.