Setting with SD Manager 3
4.
Check the analysis data (10) to see if there is any unnecessary data.
It is possible to delete unnecessary data by selecting the data on the screen and pressing the [Delete]
key. The table (7) and chart (11) will be updated each time analysis data is deleted.
If you have deleted analysis data accidentally, click the [Retrieve log] button again to recall it.
5.
Select a desired standard deviation range (9) from the pull-down menu.
6.
The flowchart below shows an example to optimize setting parameters of muting input time difference
based on analysis data.
7.
Adjusting the T1 Min and T1 Max closer to the A.D. Min and Max allows the user to keep the
productivity and improve the safety.
The following operations in Step 7 are unnecessary if the T1 Min and T1 Max are fairly close to the A.D. Min and Max.
If you change T1 Min and T1 Max, make sure that these values satisfies "T1 Min < A.D. Min < A.D. Max < T1 Max".
F3SG-SR
226
User's Manual
Analysis data is out of the range of T1 Min to T1 Max, resulting in a
muting sequence error.
Take example solutions below.
1) Delete any unnecessary analysis data (10).
2) Change T1min/T1max value in Muting setting screen.
3) Change T1min and T1max values on the muting time information
setting screen.
4) Change installation conditions and retrieve logs again.
There is analysis data out of the range of A.D. Min to Max.
Take example solutions below.
1) Delete any unnecessary analysis data (10).
2) Select another standard deviation range value.
The range of A.D. Min to Max is out of the range T1 min to T1 max.
Take example solutions below.
1) Delete any unnecessary analysis data (10).
2) Select another standard deviation range value.
3) Change T1min and T1max on the muting time information setting
screen.
Optimizing muting setting parameters
Yes
Yes
Yes
Is the range of A.D.
between T1 Min and T1 Max?
No
The muting is possible with current
productivity and improve the safety
Is judgment in chart (7) red?
No
Is judgment in chart (7) yellow?
No
Judgment in chart (7) is green.
settings and installation.
Go to Step 7 to keep the
in the current conditions.