Input/Output Circuit and Applications

6-2-1-3. Auto Reset Mode with Optical Synchronization and EDM Used

[Wiring Example]
F39-JG
Function
EDM *5
Interlock
Operating Range Selection *5 Long : Open the OPERATING RANGE SELECT INPUT line of the emitter or connect the line to 24 VDC.
Non-Muting system
External Test not used
Optical Synchronization
Timing chart
Beam state: Unblocked
Blocked
OSSD
When a functional earth is necessary, wire an earth cable according to the example in 6-2-1-1. Auto Reset Mode with
Optical Synchronization and EDM Unused. Also refer to 5-4-4. Functional Earth Connection for more information.
F3SG-SR
318
User's Manual
C-L
F39-JG
S1
KM1
KM2
DIP switch
EDM Enabled
Auto Reset (factory default setting)
Long
Perform wiring according to the wiring diagram.
N/A
Connect the TEST line of the emitter to 0V/24V of the emitter.
Do not connect the COM(+) and COM(-) lines of the of emitter and receiver with each other.
S1: Lockout reset switch
KM1, KM2: Safety relay with forcibly guided contacts (G7SA) or magnetic contactor
M: Motor
*1. Reverse the polarity of the power supply when using in the NPN system.
*2. Connect the line to 0 VDC if Operating Range Selection is used in Short Mode.
*3. Refer to 2-6. External Test for more information if External Test is used.
*4. This is the case for a PELV circuit.
*5. Set the function with the DIP Switches on the Intelligent Tap or the SD Manager
3, restore the settings to the F3SG-SR, and perform wiring according to the wiring
diagram.
C-D
KM1
KM2
*4
Setting
[External device monitoring] : Enable
[Operating Range Selection] : Long mode
[Muting] : Disable
Intelligent Tap
Needed
KM1
KM2
M
Wiring for NPN *1
24 VDC
24 VDC
: Indicates a switch position.
SD Manager 3