Installing HiPath 3000
Installing HiPath 3800
Danger
7
Each HiPath 3800 system cabinet and any patch panel (S30807-K6143-X) that may
be installed must be grounded as shown in Figure 4-13 by a separate ground con-
ductor (minimum cross-section = 2.5 mm
securely installed and strain-relieved.
If external factors can impact on the ground conductor and if protected installation is
not possible, the ground conductor must have a minimum cross-section of 4 mm
Please note:
The 19-inch cabinet's potential equalization bus may only be used if it is grounded
by a separate ground conductor.
Failure to follow these instructions can result in electrical shock.
4-28
Nur für den internen Gebrauch
2
). Make sure that the ground conductor is
A31003-H3590-S100-7-7620, 06/2012
HiPath 3000/5000 V9, Service documentation
2
.