4.2.4.2
Selecting the Installation Site
Selecting a site
The customer usually has a preferred installation site in mind, for example an existing 19-inch
cabinet.
Make sure that the customer's site meets the following guidelines:
To guarantee sufficient system ventilation, allow a minimum of 10 cm clearance around the
●
housing.
Do not expose the systems to direct sources of heat (for example sunlight and heaters).
●
Do not expose the systems to extremely dusty environments.
●
Avoid contact with chemicals.
●
Take every precaution to prevent the formation of condensation on the system during op-
●
eration. Systems covered with condensation must be dried before being used.
Observe the environmental conditions specified in Section 2.11.
●
Information on the design can be found in the following sections:
HiPath 3500 Section 2.1.4.4
●
HiPath 3300 Section 2.1.4.5
●
4.2.4.2.1
For U.S. only: Power plug
The AC connection must fulfill the requirements specified in Table 4-13.
Table 4-13
Electrical Connection Values (for U.S. only)
Nominal
Nominal voltage range
voltage
from
120 V AC/
110 V AC
60 Hz
A31003-H3590-S100-7-7620, 06/2012
HiPath 3000/5000 V9, Service documentation
Installing HiPath 3550, HiPath 3350, HiPath 3500, and HiPath 3300
Nominal Frequency
to
from
130 V AC
47 Hz
Wall Outlet Configura-
Range
to
63 Hz
NEMA 5-15, 2-pin, 3-
wire, earth
inst_h3.fm
Installing HiPath 3000
tions
4-111