3.15 Analog Nominal Value Output

PLC analog output
3.15.1 Nominal Value Output
3 – 36
Output:
Maximum load of outputs:
Maximum capacity:
13 analog outputs are available:
n
Connection X8: Analog output 1 to 6
n
Connection X9: Analog output 7 to 12
The PLC analog outputs can be controlled through Module 9130.
Please note:
n
For analog axes and analog spindle, use MP120.x and MP121.x to assign the
corresponding analog outputs on terminal X8 or X9 to the nominal speed
outputs.
n
The connecting cables to the nominal value outputs must not have more
than one intermediate terminal.
n
If you must branch to physically separate servo inputs, the connection must
be made in a grounded terminal box, e.g. Id. Nr. 251 249-01 from
HEIDENHAIN.
The housing of the terminal box must be electrically connected with the
frame of the machine.
n
The 0 V connections of the nominal-value-difference inputs must be
connected with the signal ground. Cross section ≥ 6 mm
n
Use only original HEIDENHAIN cables and connecting elements.
±10 V
2 mA
2 nF
HEIDENHAIN Technical Manual iTNC 530