Operation
6.5 Local operation
6.5.10

Position of the decimal point

Introduction
Set the position of the decimal point in mode 17. The device can display measured values
with up to four decimal places.
Procedure
To move the decimal point, proceed as follows:
1. Set mode 17.
A mask appears in the display showing the current position of the decimal point.
2. Select the desired display format.
8.8888
88.888
888.88
8888.8
88888
3. Save with the [M] button.
Note
If you set the decimal point too far to the right, the resolution of the display may be too
low. The display may show e.g. "0" instead of "0.43".
If you set the decimal point too far to the left, it can overflow. The display will then show
the character sequence 9.9.9.9.9 and error code F_004 instead of the measured value.
See also
Errors (Page 192)
6.5.11

Display of the zero-point adjustment

Introduction
The zero-point adjustment is shown in mode 18. The zero point adjustment is carried out by
the zero point calibration in mode 7 or by the calibration procedure in modes 19 and 20.
90
SITRANS P DS III/P410 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00053276-08