13.7 Operating conditions
Conditions of use for gauge pressure and absolute pressure with
flush-mounted diaphragm
Interference emission and
interference immunity
Process medium conditions
Process temperature
1)
Measuring cell with sili-
cone oil filling
Measuring cell with inert
liquid
Measuring cell with Neo-
bee (FDA-compliant)
Measuring cell with high-
temperature oil filling
Observe the temperature limits in the process connection standards (e.g. DIN 32676 and DIN 11851) for the maximum
1)
process temperature for flush-mounted process connections.
Conditions of use for pressure transmitter with PMC connection
Installation conditions
Ambient temperature
Note
Measuring cell with silicone oil
filling
Display
Storage temperature
Climate class
Condensation
Degree of protection in accord-
ance with EN 60529
Degree of protection in accord-
ance with NEMA 250
Electromagnetic compatibility
Interference emission and inter-
ference immunity
Process medium conditions
Process temperature
216
In accordance with EN 61326 and
NAMUR NE 21
-40 ... +150°C (-40 ... +302 °F)
-40 ... +200°C (-40 ... +392 °F) with
cooling extension
-20 ... +100 °C (-4 ... +212 °F)
-20 ... +200°C (-4 ... +392 °F) with
cooling extension
-10 ... +150°C (14 ... 302 °F)
-10 ... +200°C (14 ... 392 °F) with
cooling extension
-10 ... +250 °C (14 ... 482 °F) with
cooling extension
Observe the temperature class in hazardous areas.
-40 ... +85 °C (-40 ... +185 °F)
-30 ... +85 °C (-22 ... +185 °F)
-50 ... +85 °C (-58 ... +185 °F)
Permitted
IP66, IP68
NEMA 4X
In accordance with EN 61326 and NAMUR NE 21
-40 ... +100 °C (-40 ... +212 °F)
SITRANS P DS III/P410 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00053276-08