Electronics Temperature Transducer Block - Siemens SITRANS P DS III Operating Instructions Manual

Digital pressure transmitter
Hide thumbs Also See for SITRANS P DS III:
Table of Contents

Advertisement

Variable
Measurement value (pri-
mary variable)
Secondary variable 3
P
L
V
For the measurement values (primary variables) you can also set the unit "%" for all
measurement types.
Secondary variable 2 is a value normalized to one in all measurement types. The unit is fixed
at "none".
See also
Unit (Page 84)
7.1.4

Electronics temperature transducer block

The electronics temperature transducer block is manufacturer-specific and not described in
the profile. The transducer block is responsible for monitoring the internal temperature of the
device electronics. The transducer block cannot change the pressure value, only its status.
The permissible limits correspond to those of the permissible ambient temperature. If a limit
is violated, the status changes to "GOOD – Active Critical Alarm – High/Low-limit". The
status of the cleaned-up pressure value in the pressure transducer block receives the status
"UNCERTAIN – Value not accurate – high/low-limit". This procedure is accompanied by a
PROFIBUS diagnostic message "Electronics temperature too high".
There are also peak indicators for maximum and minimum values available.
See also
Min/max indicator (Page 122)
Status (Page 167)
SITRANS P DS III/P410 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00053276-08
Measurement type
Pressure
P
---
Pressure
Level
Volume
Operator control functions via PROFIBUS
7.1 Communications structure for PROFIBUS PA
Level
Volume
L
V
---
---
F
Volume flow
M
Mass flow
Volume flow
Mass flow
F
F
---
M
103