Technical data
13.2 SITRANS P DS III input
Input pressure transmitter with PMC connection
Measured variable
Span (continuously adjustable) or measur-
ing range, max. operating pressure and
max. test pressure
Lower measuring limit
Measuring cell with silicone oil filling
•
Measuring cell with inert liquid
•
Measuring cell with neobee
•
Upper measuring limit
Order the nominal measuring range with the order option Y01 for PROFIBUS PA or FOUNDATION Fieldbus.
1)
For PMC-Style Minibolt, the span should not be less than 500 mbar
2)
Absolute pressure input (from the gauge pressure series)
Measured variable
Span (continuously adjustable) or measur-
ing range, maximum operating pressure (as
per 97/23/EC pressure device guideline)
and maximum test pressure (as per
DIN 16086)
Lower measuring limit
Measuring cell with silicone oil filling
•
Measuring cell with inert liquid
•
196
Gauge pressure
Span
1) 2)
0.01 ... 1 bar
1 ... 100 kPa
0.15 ... 14.5 psi
0.04 ... 4 bar
4 ... 400 kPa
0.58 ... 58 psi
0.16 ... 16 bar
0.016... 1.6 MPa
2.3 ... 232 psi
100 mbar a/10 kPa a/1.45 psi a
2)
100 mbar a/10 kPa a/1.45 psi a
2)
100 mbar a/10 kPa a/1.45 psi a
2)
100% of maximum span
Absolute pressure
Span
1)
8.3 ... 250 mbar a
0.83 ... 25 kPa a
3 ... 100 inH
43 ... 1300 mbar a
4.3 ... 130 kPa a
17 ... 525 inH
160 ... 5000 mbar a
16 ... 500 kPa a
2.32 ... 72.5 psi a
1 ... 30 bar a
0.1 ... 3 MPa a
14.5 ... 435 psi a
0 mbar a/kPa a/psi a
Maximum operating
pressure MAWP (PS)
4 bar
400 kPa
58 psi
7 bar
700 kPa
102 psi
21 bar
2.1 MPa
305 psi
Maximum operating
pressure MAWP (PS)
1.5 bar a
150 kPa a
O a
21.8 psi a
2
2.6 bar a
260 kPa a
O a
37.7 psi a
2
10 bar a
1 MPa a
145 psi a
45 bar a
4.5 MPa a
653 psi a
Operating Instructions, 02/2016, A5E00053276-08
Maximum test pressure
6 bar
600 kPa
87 psi
10 bar
1 MPa
145 psi
32 bar
3.2 MPa
464 psi
Maximum test pressure
6 bar a
600 kPa a
87 psi a
10 bar a
1 MPa a
145 psi a
30 bar a
3 MPa a
435 psi a
100 bar a
10 MPa a
1450 psi a
SITRANS P DS III/P410 with PROFIBUS PA