Installing / mounting

4.1

Basic safety instructions

Wetted parts unsuitable for the process media
Danger of injury or damage to device.
Hot, toxic and corrosive media could be released if the process medium is unsuitable for
the wetted parts.
• Ensure that the material of the device parts wetted by the process medium is suitable for
Incorrect material for the diaphragm in Zone 0
Danger of explosion in the hazardous area. If operated with intrinsically safe supply devices
of category "ib" or devices of the flameproof enclosure version "Ex d" and simultaneous use
in Zone 0, pressure transmitter explosion protection depends on the tightness of the
diaphragm.
• Ensure that the material used for the diaphragm is suitable for the process medium.
Unsuitable connecting parts
Danger of injury or poisoning.
In case of improper mounting hot, toxic and corrosive process media could be released at
the connections.
• Ensure that connecting parts (such as flange gaskets and bolts) are suitable for
Note
Material compatibility
Siemens can provide you with support concerning selection of sensor components wetted by
process media. However, you are responsible for the selection of components. Siemens
accepts no liability for faults or failures resulting from incompatible materials.
SITRANS P DS III/P410 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00053276-08
WARNING
the medium. Refer to the information in "Technical data" (Page 193).
WARNING
Refer to the information in the section "Technical data (Page 193)".
WARNING
connection and process media.